The customer main requirements are:
1. Heating to 200 degrees within 10 minutes
2. The temperature can be maintained at around 200 degrees without significant changes
3. Save raw material costs
4. Heating space size 6m*3m*2m
Our recommendations:
Power calculation (accurate version)
Key parameters:
●Space volume: 6×3×2=36m³
●Temperature rise requirement: 20℃→200℃ (ΔT=180℃)
●Heating time: 10 minutes (0.167 hours)
●Air density: 1.293kg/m³ (20℃)
●Air specific heat capacity: 1.005kJ/(kg·K)
●Thermal efficiency: calculated as 85% (typical value of diesel burner)
Calculation formula:
Q = (m×c×ΔT)/(η×t)
= (36×1.293×1.005×180)/(0.85×0.167)
≈ 58,200kJ/h ≈ 162kW
Recommended power: 180-200kW (considering 20% safety margin)